(+65) 6931 4598
sales@glo-jupiter.com
6D Mandai Estate #09-11 M-Space

MicroVision Condensate

Overview

The MicroVision Condensate Controller delivers condensate return monitoring with a reliable and accurate temperature compensated conductivity probe. Worry less about installation with ‘plug and play’ simplicity with user friendly easy to use programming to save time and money on equipment installation. This latest addition to the MicroVision family of controllers is configured specifically for precise measurement of conductivity in the condensate return and allows for more efficient use of time in inhibiting corrosion.

General Specifications

Enclosures NEMA 4X / IP65
Conductivity Range 0-20,000 μS/cm
Power Input 100-240 VAC +/-10% / 50/60Hz / 5A
Controller Display LCD
Timers Selectable:, Pulse, Limit, Percent, 28 Day, Cycle
Outputs 5 Output Relays – 1 powered for motorized ball valves or solenoid blowdown valves / 3 powered for chemical metering pumps / 1 dry contact for remote alarm, 4-20mA Output – Isolated / Scalable
Inputs 5 Digital Inputs Total, Drum Level, Dry Contact Water Meter, Hall Effect, Boiler Interlock
Selectable Sampling Modes Continuous, Timed Sample, Sample and Hold
Controls Programmable Inputs: Drum level – Dry contact water meter – Hall effect – Boiler interlock, Selectable Timers: 28 day – Pulse – Limit – Percent – Cycle, 5 Output Relays, 4-20mA Output
Accessories
  • Flow Control Valves
  • PULSAtron Electronic Metering Pumps
  • Sample Coolers
  • Valve Packages
  • Water Meters

Sensor Specifications

Sensor Temperature 392 degree F / 220 degree C
Sensor Pressure 250 PSI (17 BAR)
Sensor Saturated Steam 210 psi/14.4 bar
Sensor Cable Length 25 feet max. use of the supplied cable is required

Features

  • Simple Programming – Factory preset to operate in timed sample mode right out of the box
  • Easy installation and easy to use
  • Reliable Conductivity Probe – Temperature compensated for accurate readings
  • Selectable Sampling Modes – Continuous / Timed Sample / Sample & Hold, 5 output relays
  • Selectable timers
  • 5 digital inputs
  • 4-20mA output
  • Heavy duty enclosure